The everyday profile caps grid charging at 54V, so the bank can go weeks without a full charge and the EG4 BMS coulomb counters drift (proven: pack 6 read 76% SoC while at the same 53.4V/3.337V-per-cell as packs reading 50-55% — all paralleled, so physically equal charge; the spread is pure drift). - profiles/eg4-lp4-v2-calibration.yaml: temporary profile, identical to canonical except stop_charge_voltage 54.0 -> 0 (Full), so grid can finish a full charge to the 56.4V absorption hold that re-anchors every pack to 100%. - calibration-charge skill: guided runbook (pre-flight safety, two methods solar-only / grid-assist, live monitoring with cell-voltage/temp aborts, re-anchor verification, mandatory revert). - REFERENCE: scoped action-policy exception (this skill alone may flip stop_charge, both units, user-confirmed, must revert); corrected pack-6 / SoC-drift notes to the verified equal-voltage-different-SoC signature. Co-Authored-By: Claude Opus 4.8 (1M context) <noreply@anthropic.com>
8.9 KiB
Solar install — system map (shared reference for the solar skills)
This file is the ground truth the solar-* / troubleshoot-* / power-usage
skills build on. Read it once at the start of any solar task. Everything below
was verified live on this host (the monitoring Pi) on 2026-06-23; re-verify
anything load-bearing before acting on it.
Topology
6× EG4 LifePower4 v2 packs ──RS485 (1 FTDI each)──┐
2× MPP Solar LVX6048 inverters ──USB-HID/PI18─────┤ this Pi ──MQTT──► HA broker
1× OpenEVSE charger (10.0.0.249) ──its own WiFi───┘ (daemons) 10.0.0.41:1883
All telemetry lands on the MQTT broker at 10.0.0.41:1883 under HA
auto-discovery (homeassistant/<class>/<entity>/config retained, .../state
republished each poll cycle — state topics are NOT retained, so to read
current values you must listen for a window: use lib/solar-snapshot).
Broker credentials live in ~/.config/powermon/powermon.yaml
(mqttbroker.{name,port,username,password}). Never hardcode them — every
tool here reads them from that file. lib/solar-snapshot does too.
The snapshot helper
./lib/solar-snapshot (relative to this skills dir) captures the latest value of
every matching MQTT topic over a short window and prints a table. This is the
primary read tool — prefer it over raw mosquitto_sub.
solar-snapshot [-w SECONDS] [-g GREP_RE] [-f] TOPIC_FILTER...
MQTT + matches one WHOLE level, so lifepower4_+ matches nothing. Subscribe to
homeassistant/sensor/+/state and narrow with -g:
solar-snapshot -g 'lvx6048_1_' 'homeassistant/sensor/+/state'
solar-snapshot -w 16 -g 'lifepower4_[1-6]_soc/' 'homeassistant/sensor/+/state'
solar-snapshot 'openevse/#' # EVSE publishes on-change; idle when unplugged
The history helper
solar-snapshot only sees now. For "when did X last happen / show last week",
use ./lib/ha-history, which queries Home Assistant's recorder (the only
store that keeps history — local journald is volatile, ~1 day, wiped on reboot;
no solar data goes to InfluxDB). Default window 7 days; HA recorder default
retention is 10 days.
ha-history [-s SINCE] [-e END] [-m REGEX] [-a] ENTITY...
ha-history -s "10 days ago" sensor.lvx6048_lvx6048_1_device_mode sensor.lvx6048_lvx6048_2_device_mode
ha-history -s "10 days ago" -m fault sensor.lvx6048_01_lvx6048_1_fault_code sensor.lvx6048_02_lvx6048_2_fault_code
HA entity_ids ≠ MQTT object names. powermon's hass output doubles the device slug and is inconsistent across commands, so you must use the real ids, e.g.:
- device mode:
sensor.lvx6048_lvx6048_{1,2}_device_mode(device sluglvx6048) - fault code:
sensor.lvx6048_0{1,2}_lvx6048_{1,2}_fault_code(sluglvx6048_01/_02) - PV/batt/load:
sensor.lvx6048_lvx6048_1_{mppt1_input_power,mppt1_input_voltage,battery_voltage,ac_output_active_power} - EG4 packs follow the same doubling, e.g.
sensor.lifepower4_*. When unsure, list them:curl -s -H "Authorization: Bearer $(cat ~/.config/ha/token)" $HA/api/states | python3 -c 'import sys,json;[print(s["entity_id"]) for s in json.load(sys.stdin) if "lvx6048" in s["entity_id"]]'Auth: reads a long-lived token from~/.config/ha/token(mode 600) or$HA_TOKEN— never on the command line, never hardcoded. Base URL$HA_URLelse~/.config/ha/urlelsehttp://10.0.0.41:8123. If it reports "no token", the user must create one (HA → Profile → Security → Long-lived access tokens) and write it to~/.config/ha/token; tell them which file, don't ask them to paste it in chat. Recorder excludes (pereg4battery/homeassistant/recorder.yaml) drop EG4 per-cell/register/string entities — those have no history; the inverterdevice_mode/fault_codeand packsoc/pack_voltageetc. are recorded.
Services (this Pi)
| Service | Role | Entities it feeds |
|---|---|---|
powermon.service |
LVX6048 #1 poller (PI18/USB) | lvx6048_1_* |
powermon2.service |
LVX6048 #2 poller (PI18/USB) | lvx6048_2_* |
lvx-resolve-links.service |
oneshot: maps /dev/hidraw* → /dev/lvx6048-{1,2} by PI18 serial; runs before powermon |
(links) |
lvx-control.service |
bridges solar/control/lvx6048/* → powermon adhoc queue |
(control) |
eg4-battery.service |
polls all 6 packs over RS485/Modbus | lifepower4_1..6_* |
Quick health: systemctl is-active powermon.service powermon2.service eg4-battery.service lvx-control.service
Logs: journalctl -u <svc> --since "10 min ago" --no-pager
Entities cheat-sheet
Inverters lvx6048_{1,2}_* (PI18 GS/MOD/PIRI/FWS/ET):
device_mode (Power-On/Standby/Bypass/Battery/Fault/Charge…), fault_code,
battery_voltage, battery_capacity (%), ac_output_active_power (W),
ac_output_voltage, grid_voltage, mppt1_input_power/mppt2_input_power (W, PV),
inverter_heat_sink_temperature, parallel_instance_number (0 = master, 1+ = slave).
Packs lifepower4_{1..6}_* (Modbus): soc, soc_alt, pack_voltage,
pack_current (signed, + = charging), cell_01..16_voltage,
cell_voltage_delta_mv (imbalance), cell_voltage_min/max, capacity_ah,
temperature_01..04, temperature_pcb, model, firmware_version,
firmware_date, warning/protection bits, register_NN raw. There are 16 cells/pack.
EVSE openevse/<key> and openevse_* HA entities: power (W), voltage,
amp (mA raw → A in HA), pilot, max_current, session_energy (Wh),
total_energy, status (active/sleeping/disabled…), state, temp,
vehicle (plug). Charger HTTP UI at http://10.0.0.249.
Derived HA template sensors (lifepower4_N_pack_power, _temperature_max,
_cell_imbalance_pct, lifepower4_stack_*) are computed inside HA, not on
MQTT — compute them yourself from the raw entities when working off the Pi.
Known issues / gotchas (check memory for the canonical versions)
- Inverter
battery_voltageis INTERMITTENTLY wrong — read a correct ~54 V on 2026-06-20 (verified via HA history), but ~9–10 V on 2026-06-23/24 after the Jun 22 14:18 reboot, with packs steady at ~52–53 V throughout. So it's a post-reboot / re-init glitch (the inverter or PI18 GS field not settling after restart), NOT a permanent scaling bug. Implication: treat the inverter battery reading as untrustworthy and use thelifepower4_*pack entities for any battery math; if it reads ~10 V right now, a powermon (or inverter) restart may clear it — worth testing. - Pack 6 is an oddball: Modbus addr
0x01@ 115200 (packs 1–5 are0x40@ 9600). It reads SoC high (76 % on 2026-06-24 vs 50–55 % on packs 1–5) — but at the SAME pack_voltage (53.4 V) and cell voltage (3.337 V), so that's counter drift, not real imbalance: all packs are paralleled and physically at the same charge. - EG4 SoC never re-anchors (drifts because packs rarely hit 100 % to reset the
coulomb counter). Verified live via the equal-voltage/different-SoC signature above.
Fix = the
calibration-chargeskill (periodic full charge). See memoryproject_eg4_soc_drift_remediation. - RS485 daisy-chain silences slave packs — each pack needs its own FTDI; an
inter-pack chain demotes slaves. See memory
project_eg4_daisy_chain_silences_slaves. - No per-day inverter energy — PI18 only gives
ET(lifetime Wh); ED/EM/EY NAK. Daily kWh must come from HA recorder or ET deltas. - Parallel cluster: changing inverter settings on only one unit risks fault 86
(desync).
lvx-controlalways mirrors to both — that's why setters go through it.
Action policy for these skills
Allowed (safe remediation):
- Read anything:
solar-snapshot,mosquitto_sub,journalctl,systemctl status/is-active. - Restart the data-plane daemons when they're wedged:
sudo systemctl restart powermon.service/powermon2.service/eg4-battery.service/lvx-control.service - Recover inverter USB links:
sudo systemctl restart lvx-resolve-links.serviceorsudo /usr/local/sbin/lvx-resolve-links.
Forbidden (escalate to the user instead — propose the exact command, don't run it):
- Any inverter/battery setter:
solar/control/lvx6048/*publishes (charger priority, max charge current, output priority, …). lvx-flash/flash.py applyanddump/compare/sync-check— they contend for exclusive USB and stop powermon; advanced, user-driven only.- Anything that writes battery thresholds, output mode, or factory resets.
- Power-cycling hardware, moving cables, breaker changes.
When a fix is outside the allowed set, report the finding and hand the user the precise command(s) to run.
Scoped exception — calibration-charge skill only: that one skill may change
exactly one setting (stop_charge_voltage → Full and back) via the prepared
eg4-lp4-v2-calibration.yaml profile, on BOTH inverters, and ONLY after explicit
in-session user confirmation, and it must REVERT afterward. No other skill and no
other setting. This does not loosen the policy above for anything else.