noise 56b2cc2bf1 Add calibration-charge skill to fix EG4 SoC counter drift (improvement #1)
The everyday profile caps grid charging at 54V, so the bank can go weeks
without a full charge and the EG4 BMS coulomb counters drift (proven: pack 6
read 76% SoC while at the same 53.4V/3.337V-per-cell as packs reading 50-55%
— all paralleled, so physically equal charge; the spread is pure drift).

- profiles/eg4-lp4-v2-calibration.yaml: temporary profile, identical to
  canonical except stop_charge_voltage 54.0 -> 0 (Full), so grid can finish a
  full charge to the 56.4V absorption hold that re-anchors every pack to 100%.
- calibration-charge skill: guided runbook (pre-flight safety, two methods
  solar-only / grid-assist, live monitoring with cell-voltage/temp aborts,
  re-anchor verification, mandatory revert).
- REFERENCE: scoped action-policy exception (this skill alone may flip
  stop_charge, both units, user-confirmed, must revert); corrected pack-6 /
  SoC-drift notes to the verified equal-voltage-different-SoC signature.

Co-Authored-By: Claude Opus 4.8 (1M context) <noreply@anthropic.com>