Commit Graph

3 Commits

Author SHA1 Message Date
f1128e807a Record decision to keep 48.0V discharge floor (improvement #3)
Reviewed the cutoff/stop-discharge floor; deliberately kept at 48.0V (3.00
V/cell) for cycle-life margin. Lowering to 46-47V unlocks only a few % of LFP
capacity and isn't worth deeper cycling on this large, non-capacity-constrained
bank. Comment only; no value change.

Co-Authored-By: Claude Opus 4.8 (1M context) <noreply@anthropic.com>
2026-06-24 12:28:44 -04:00
b5b69f95c1 Correct EG4 profile sizing 3->6 packs; keep 60A charge cap (improvement #2)
- eg4-lp4-v2.yaml: rationale updated 300Ah->600Ah/~30.7kWh; 120A combined is
  now ~0.2C. Charge current deliberately NOT raised to 80A: not clipping — at
  solar noon on a clear day (2026-06-24, ~5.8kW PV) the bank took only 71A of
  the 120A cap. Real harvest limiter is PV (5.8 of 14.4kW nameplate, suspected
  down strings), not the ceiling.
- REFERENCE: pack HA entity_ids are triple-prefixed
  (sensor.eg4_lifepower4_lifepower4_1_lifepower4_1_*) — discover, don't construct.

No setting values changed; documentation/accuracy only.

Co-Authored-By: Claude Opus 4.8 (1M context) <noreply@anthropic.com>
2026-06-24 12:25:48 -04:00
00ab311d92 working in production - not entirely validated. parallel mode working. 2026-04-26 19:26:44 -04:00