- eg4-lp4-v2.yaml: rationale updated 300Ah->600Ah/~30.7kWh; 120A combined is now ~0.2C. Charge current deliberately NOT raised to 80A: not clipping — at solar noon on a clear day (2026-06-24, ~5.8kW PV) the bank took only 71A of the 120A cap. Real harvest limiter is PV (5.8 of 14.4kW nameplate, suspected down strings), not the ceiling. - REFERENCE: pack HA entity_ids are triple-prefixed (sensor.eg4_lifepower4_lifepower4_1_lifepower4_1_*) — discover, don't construct. No setting values changed; documentation/accuracy only. Co-Authored-By: Claude Opus 4.8 (1M context) <noreply@anthropic.com>
67 lines
3.1 KiB
YAML
67 lines
3.1 KiB
YAML
# LVX6048 settings profile — EG4 LifePower4 v2 LiFePO4 bank, open-loop.
|
||
#
|
||
# Designed for: 6× EG4 LP4 v2 100 Ah in parallel (600 Ah, ~30.7 kWh).
|
||
# (Was 3 packs originally; 3 more added — commit 38ac9ca. Values below are
|
||
# unchanged and remain correct for 6 packs — they're only MORE conservative now.)
|
||
# Apply identically to both inverters in a parallel pair:
|
||
# sudo systemctl stop powermon.service powermon2.service
|
||
# ./flash.py apply --device /dev/lvx6048-1 --profile profiles/eg4-lp4-v2.yaml --confirm
|
||
# ./flash.py apply --device /dev/lvx6048-2 --profile profiles/eg4-lp4-v2.yaml --confirm
|
||
# sudo systemctl start powermon.service powermon2.service
|
||
# ./flash.py compare --device-a /dev/lvx6048-1 --device-b /dev/lvx6048-2
|
||
# ./flash.py sync-check --device-a /dev/lvx6048-1 --device-b /dev/lvx6048-2
|
||
#
|
||
# Voltage rationale (16S LFP, 3.2 V/cell nominal = 51.2 V pack):
|
||
# bulk 56.4 V = 3.525 V/cell — long-life sweet spot for LFP
|
||
# float 54.0 V = 3.375 V/cell — rest near mid-knee, avoid sitting on the top
|
||
# stop_charge 54.0 V — grid charges only to ~mid-knee; solar handles the bulk top-off
|
||
# stop_dis 48.0 V = 3.000 V/cell — soft "switch to grid" point
|
||
# cutoff 48.0 V = 3.000 V/cell — inverter hard shutdown floor (BMS still protects below)
|
||
# Conservative off-grid policy: keep grid as a soft top-up, let solar do the bulk work.
|
||
#
|
||
# Current rationale (600 Ah bank):
|
||
# 60 A/unit × 2 units = 120 A combined ≈ 0.2 C — very gentle on a 600 Ah bank.
|
||
# 30 A/unit MUCHGC keeps grid-charging conservative (60 A combined).
|
||
# NOT raised to 80 A/unit (the enum max): charging is not clipping — at solar noon
|
||
# on a clear day (2026-06-24, ~5.8 kW PV) the bank drew only 71 A of the 120 A cap.
|
||
# The real harvest limiter is PV production (~5.8 kW seen vs 14.4 kW nameplate —
|
||
# the suspected down strings), not the charge ceiling. Revisit only if PV is
|
||
# restored and midday charge current is seen pinned at ~120 A below ~90% SoC.
|
||
|
||
# enum: AGM | FLOODED | USER
|
||
# USER required to enable the per-cell custom voltages below.
|
||
battery_type: USER
|
||
|
||
# V 40.0..48.0 — hard shutdown; must be < stop_discharge_voltage.
|
||
cutoff_voltage: 48.0
|
||
|
||
# V 44.0..51.0 — switch battery→grid below this (pair: stop_charge_voltage).
|
||
stop_discharge_voltage: 48.0
|
||
|
||
# V 0 (=Full) or 48.0..58.0 — switch grid→battery above this. 0 = let bulk define.
|
||
stop_charge_voltage: 54.0
|
||
|
||
# V 48.0..58.4 — CC→CV transition (pair: float_voltage; must be >= float_voltage).
|
||
bulk_voltage: 56.4
|
||
|
||
# V 48.0..58.4 — held while on grid (pair: bulk_voltage; must be <= bulk_voltage).
|
||
float_voltage: 54.0
|
||
|
||
# A 10,20,30,40,50,60,70,80 — combined solar+AC cap, per unit.
|
||
max_charging_current: 60
|
||
|
||
# A 2,10,20,30,40,50,60,70,80 — grid-side cap, per unit.
|
||
max_utility_charging_current: 30
|
||
|
||
# enum: solar_utility_battery | solar_battery_utility
|
||
output_source_priority: solar_battery_utility
|
||
|
||
# enum: solar_first | solar_and_utility | solar_only
|
||
charger_priority: solar_first
|
||
|
||
# enum: battery_load_utility_ac | load_battery_utility
|
||
solar_power_priority: battery_load_utility_ac
|
||
|
||
# enum: enabled | disabled (PEI/PDI)
|
||
grid_tie: disabled
|