# lvx-flash
Apply declarative YAML settings profiles to an LVX6048 inverter via PI18.
Reuses the patched `powermon` install at `~/.local/share/uv/tools/powermon/` — the shebang in `flash.py` points there, so no extra setup is needed.
## Commands
```bash
# 1. Snapshot the inverter's current settings into an editable profile.
./flash.py dump --out profiles/current.yaml
# 2. Copy/edit. Preview the diff against the live device at any time.
./flash.py diff --profile profiles/winter.yaml
# 3. Apply. The tool stops powermon.service for the duration, writes each
# changed setting via the corresponding PI18 set command, verifies via
# PIRI readback, and restarts powermon.service at the end.
./flash.py apply --profile profiles/winter.yaml --confirm
# 4. Compare two inverters live (for parallel setups). Exits 0 if identical,
# 1 if divergent. Useful as a quick "are the two in sync?" check.
./flash.py compare --device-a /dev/lvx6048-1 --device-b /dev/lvx6048-2
# 5. Runtime sync-check for paralleled units. Reads GS+FWS+MOD+VFW from each
# and reports firmware mismatch, parallel-valid flag, active fault codes,
# mode mismatch, AC voltage/frequency divergence. Exits 0 on pass, 1 on fail.
./flash.py sync-check --device-a /dev/lvx6048-1 --device-b /dev/lvx6048-2
```
Device selection on every subcommand:
- `--serial SN` (default — uses `SERIAL_UNIT_1` for single-device commands, `SERIAL_UNIT_{1,2}` for pairs) — globs `/dev/hidraw*` and picks the one whose PI18 `ID` matches. Resilient to cable moves.
- `--device PATH` — explicit hidraw path, skips auto-resolution. Useful for probing an unknown unit.
The known-stack serials are hard-coded as `SERIAL_UNIT_1` / `SERIAL_UNIT_2` constants at the top of `flash.py`; edit them if a unit is replaced.
`sync-check` depends on the `FWS` / `PGS` additions to `powermon/protocols/pi18.py`; the `--serial` flow depends on the `UsbPortConfig.serial_number` field addition. Both are described in `Install.md` §5(d)(e).
## Profile schema
All keys are optional. Only present keys are applied; the rest are left alone.
| key | range / enum | PI18 setter |
|----------------------------------|------------------------------------------------------------------|-------------|
| `battery_type` | `AGM` \| `FLOODED` \| `USER` | PBT |
| `cutoff_voltage` | 40.0 48.0 V | PSDV |
| `stop_discharge_voltage` | 44.0 51.0 V | BUCD (pair) |
| `stop_charge_voltage` | 0 (full) or 48.0 58.0 V | BUCD (pair) |
| `bulk_voltage` | 48.0 58.4 V | MCHGV (pair)|
| `float_voltage` | 48.0 58.4 V (≤ bulk_voltage) | MCHGV (pair)|
| `max_charging_current` | 10, 20, 30, 40, 50, 60, 70, 80 A | MCHGC |
| `max_utility_charging_current` | 2, 10, 20, 30, 40, 50, 60, 70, 80 A | MUCHGC |
| `output_source_priority` | `solar_utility_battery` \| `solar_battery_utility` | POP |
| `charger_priority` | `solar_first` \| `solar_and_utility` \| `solar_only` | PCP |
| `solar_power_priority` | `battery_load_utility_ac` \| `load_battery_utility` | PSP |
| `grid_tie` | `enabled` \| `disabled` | PEI / PDI |
Pair settings (BUCD, MCHGV) must have both halves present.
## Safety
- `apply` refuses to run without `--confirm`.
- Range + consistency validation runs before any write. A failure aborts before touching the inverter.
- Each write is followed by a PIRI readback that must match to within 0.05 V. A mismatch aborts.
- Settings are applied in an order that's safe for a battery: cutoff → BUCD → MCHGV → currents → priorities → grid-tie mode.
- `powermon.service` is stopped for the write window so the two processes don't fight over `/dev/lvx6048-1`, then restarted even if the run aborts.
## Caveats
- Parallel setups: PCP / MCHGC / MUCHGC are indexed by parallel unit (the tool sends unit 0 — master). Some firmware only accepts sets on the master; the slave mirrors silently.
- `PIRI` reports `max_charging_current` as the effective combined (solar + AC) cap, which can exceed MCHGC's 80 A range. `dump` omits it with a comment when that happens.
- Changing `battery_type` while the unit is actively charging is generally allowed by the firmware but not recommended.