Correct EG4 profile sizing 3->6 packs; keep 60A charge cap (improvement #2)
- eg4-lp4-v2.yaml: rationale updated 300Ah->600Ah/~30.7kWh; 120A combined is now ~0.2C. Charge current deliberately NOT raised to 80A: not clipping — at solar noon on a clear day (2026-06-24, ~5.8kW PV) the bank took only 71A of the 120A cap. Real harvest limiter is PV (5.8 of 14.4kW nameplate, suspected down strings), not the ceiling. - REFERENCE: pack HA entity_ids are triple-prefixed (sensor.eg4_lifepower4_lifepower4_1_lifepower4_1_*) — discover, don't construct. No setting values changed; documentation/accuracy only. Co-Authored-By: Claude Opus 4.8 (1M context) <noreply@anthropic.com>
This commit is contained in:
@@ -1,6 +1,8 @@
|
||||
# LVX6048 settings profile — EG4 LifePower4 v2 LiFePO4 bank, open-loop.
|
||||
#
|
||||
# Designed for: 3× EG4 LP4 v2 100 Ah in parallel (300 Ah, ~15.4 kWh).
|
||||
# Designed for: 6× EG4 LP4 v2 100 Ah in parallel (600 Ah, ~30.7 kWh).
|
||||
# (Was 3 packs originally; 3 more added — commit 38ac9ca. Values below are
|
||||
# unchanged and remain correct for 6 packs — they're only MORE conservative now.)
|
||||
# Apply identically to both inverters in a parallel pair:
|
||||
# sudo systemctl stop powermon.service powermon2.service
|
||||
# ./flash.py apply --device /dev/lvx6048-1 --profile profiles/eg4-lp4-v2.yaml --confirm
|
||||
@@ -17,9 +19,14 @@
|
||||
# cutoff 48.0 V = 3.000 V/cell — inverter hard shutdown floor (BMS still protects below)
|
||||
# Conservative off-grid policy: keep grid as a soft top-up, let solar do the bulk work.
|
||||
#
|
||||
# Current rationale (300 Ah bank):
|
||||
# 60 A/unit × 2 units = 120 A combined ≈ 0.4 C — well under bank's continuous spec
|
||||
# 30 A/unit MUCHGC keeps grid-charging conservative (60 A combined)
|
||||
# Current rationale (600 Ah bank):
|
||||
# 60 A/unit × 2 units = 120 A combined ≈ 0.2 C — very gentle on a 600 Ah bank.
|
||||
# 30 A/unit MUCHGC keeps grid-charging conservative (60 A combined).
|
||||
# NOT raised to 80 A/unit (the enum max): charging is not clipping — at solar noon
|
||||
# on a clear day (2026-06-24, ~5.8 kW PV) the bank drew only 71 A of the 120 A cap.
|
||||
# The real harvest limiter is PV production (~5.8 kW seen vs 14.4 kW nameplate —
|
||||
# the suspected down strings), not the charge ceiling. Revisit only if PV is
|
||||
# restored and midday charge current is seen pinned at ~120 A below ~90% SoC.
|
||||
|
||||
# enum: AGM | FLOODED | USER
|
||||
# USER required to enable the per-cell custom voltages below.
|
||||
|
||||