2026-05-01 — fix 5-minute spikes on AC-output power time-series
Symptom
On both inverters' apparent-power and active-power Influx series, a tall rectangular spike to exactly 6000 VA / 6000 W appeared every ~5 minutes. The spike was simultaneous on both units even though they are not paralleled on AC output (and on this rig the AC outputs aren't even tied to a common load), which ruled out any real-load mechanism.
90-min sample (idle unit 2, baseline ~47 VA / ~0 W):
| metric | spike value | spike count | inter-spike gap |
|---|---|---|---|
VA |
6000 (only) | 36 / 30 min | pairs ~3–5s, 298s between pairs |
W |
6000 (only) | 12 / 30 min | same pattern |
Unit 1 spiked at :37:12 / :42:15 / :47:17 / …, unit 2 at :37:44 / :42:46 / ….
Each cycle is exactly 5 min; the two daemons sit ~32 s out of phase, so on
charts binned > 1 min they look simultaneous.
Root cause
6000 is the LVX6048's nameplate apparent / active power. Two PI18
commands return that field:
GS(every 5 s): live measurementPIRI(every 300 s): nameplate / configured rating
In powermon-patches/pi18.py both fields share the same description
string ("AC Output Apparent Power", "AC Output Active Power").
Powermon's outputformats/hass.py slugifies description into the HA
entity_id with no per-command namespace, so both publish to:
homeassistant/sensor/lvx6048_X_ac_output_apparent_power/state
homeassistant/sensor/lvx6048_X_ac_output_active_power/state
Every 300 s when PIRI fires, the entity is written with 6000 for one
publish; the next GS (≤5 s later) restores the live value. HA's recorder
captures both → Influx records a 6000-valued sample tagged to the live
entity. Hence the periodic rectangular spike.
The same collision exists for several other PIRI fields whose descriptions duplicate live GS fields:
AC Input VoltageAC Input Current(not in GS, but shadows the live current series via PIRI's nameplate input rating)AC Output VoltageAC Output FrequencyAC Output CurrentBattery Voltage
Same artifact, just less visible because nameplate values for those are close to live values during steady-state operation.
Fix
Add excl_filter to the PIRI command block in both powermon configs
(matches the existing pattern used on GS for dead/dummy fields). PIRI's
job in this stack is to publish configured thresholds — bulk/float
voltages, charging-current ceilings, source priorities, etc. The fields
that duplicate GS measurements provide no value and only corrupt the
recorder series.
- command: PIRI
trigger:
every: 300
outputs:
- type: mqtt
topic: powermon/lvx6048_X/PIRI
format:
type: hass
discovery_prefix: homeassistant
entity_id_prefix: lvx6048_X
excl_filter: '^(ac_input_voltage|ac_input_current|ac_output_voltage|ac_output_frequency|ac_output_current|ac_output_apparent_power|ac_output_active_power|battery_voltage)$'
Applied to both config/powermon/powermon.yaml and …/powermon2.yaml,
and mirrored to the live ~/.config/powermon/ deploys.
Net effect
| Metric | Before | After |
|---|---|---|
VA series spurious 6000 spikes / 5 min |
2/inverter | 0 |
W series spurious 6000 spikes / 5 min |
2/inverter | 0 |
| PIRI fields published per inverter | 26 | 18 |
| PIRI fields kept (battery/charge/priority configs) | — | all retained |
PIRI configuration entities (battery thresholds, MCHGC ceilings, output priority, etc.) are unchanged — they continue to update every 300 s on their own entity_ids.
Files touched
M LVX6048/config/powermon/powermon.yaml (excl_filter on PIRI)
M LVX6048/config/powermon/powermon2.yaml (same)
A LVX6048/2026-05-01.md (this file)
How to verify
sudo systemctl restart powermon.service powermon2.service
# Watch one PIRI cycle (≤5 min) — apparent power should NOT publish a 6000:
mosquitto_sub -h 10.0.0.41 -u mqtt -P <pass> \
-t 'homeassistant/sensor/lvx6048_+_ac_output_apparent_power/state' -W 360
# Or query Influx after one full cycle:
influx -host 10.0.0.41 -username homeassistant -password <pass> \
-database homeassistant -execute "
SELECT count(\"value\") FROM \"VA\"
WHERE (\"entity_id\" = 'lvx6048_lvx6048_1_ac_output_apparent_power'
OR \"entity_id\" = 'lvx6048_lvx6048_2_ac_output_apparent_power')
AND \"value\" = 6000
AND time > now() - 30m"
# Expect: count → 0 once the next two PIRI cycles have passed without spikes.
Rollback
git -C ~/solar checkout HEAD~1 -- LVX6048/config/powermon/
cp ~/solar/LVX6048/config/powermon/powermon{,2}.yaml ~/.config/powermon/
# (re-edit ~/.config/powermon/*.yaml to restore real MQTT_PASSWORD)
sudo systemctl restart powermon.service powermon2.service
Upstream-fix candidate
Cleaner (but invasive) alternative would patch outputformats/hass.py to
namespace entity_ids by command (e.g., _settings_ infix for PIRI). Not
worth the patch maintenance — the excl_filter is one line per command
and survives powermon upgrades.