2026-05-01 — fix 5-minute spikes on AC-output power time-series

Symptom

On both inverters' apparent-power and active-power Influx series, a tall rectangular spike to exactly 6000 VA / 6000 W appeared every ~5 minutes. The spike was simultaneous on both units even though they are not paralleled on AC output (and on this rig the AC outputs aren't even tied to a common load), which ruled out any real-load mechanism.

90-min sample (idle unit 2, baseline ~47 VA / ~0 W):

metric spike value spike count inter-spike gap
VA 6000 (only) 36 / 30 min pairs ~35s, 298s between pairs
W 6000 (only) 12 / 30 min same pattern

Unit 1 spiked at :37:12 / :42:15 / :47:17 / …, unit 2 at :37:44 / :42:46 / …. Each cycle is exactly 5 min; the two daemons sit ~32 s out of phase, so on charts binned > 1 min they look simultaneous.

Root cause

6000 is the LVX6048's nameplate apparent / active power. Two PI18 commands return that field:

  • GS (every 5 s): live measurement
  • PIRI (every 300 s): nameplate / configured rating

In powermon-patches/pi18.py both fields share the same description string ("AC Output Apparent Power", "AC Output Active Power"). Powermon's outputformats/hass.py slugifies description into the HA entity_id with no per-command namespace, so both publish to:

homeassistant/sensor/lvx6048_X_ac_output_apparent_power/state
homeassistant/sensor/lvx6048_X_ac_output_active_power/state

Every 300 s when PIRI fires, the entity is written with 6000 for one publish; the next GS (≤5 s later) restores the live value. HA's recorder captures both → Influx records a 6000-valued sample tagged to the live entity. Hence the periodic rectangular spike.

The same collision exists for several other PIRI fields whose descriptions duplicate live GS fields:

  • AC Input Voltage
  • AC Input Current (not in GS, but shadows the live current series via PIRI's nameplate input rating)
  • AC Output Voltage
  • AC Output Frequency
  • AC Output Current
  • Battery Voltage

Same artifact, just less visible because nameplate values for those are close to live values during steady-state operation.

Fix

Add excl_filter to the PIRI command block in both powermon configs (matches the existing pattern used on GS for dead/dummy fields). PIRI's job in this stack is to publish configured thresholds — bulk/float voltages, charging-current ceilings, source priorities, etc. The fields that duplicate GS measurements provide no value and only corrupt the recorder series.

  - command: PIRI
    trigger:
      every: 300
    outputs:
      - type: mqtt
        topic: powermon/lvx6048_X/PIRI
        format:
          type: hass
          discovery_prefix: homeassistant
          entity_id_prefix: lvx6048_X
          excl_filter: '^(ac_input_voltage|ac_input_current|ac_output_voltage|ac_output_frequency|ac_output_current|ac_output_apparent_power|ac_output_active_power|battery_voltage)$'

Applied to both config/powermon/powermon.yaml and …/powermon2.yaml, and mirrored to the live ~/.config/powermon/ deploys.

Net effect

Metric Before After
VA series spurious 6000 spikes / 5 min 2/inverter 0
W series spurious 6000 spikes / 5 min 2/inverter 0
PIRI fields published per inverter 26 18
PIRI fields kept (battery/charge/priority configs) all retained

PIRI configuration entities (battery thresholds, MCHGC ceilings, output priority, etc.) are unchanged — they continue to update every 300 s on their own entity_ids.

Files touched

M  LVX6048/config/powermon/powermon.yaml      (excl_filter on PIRI)
M  LVX6048/config/powermon/powermon2.yaml     (same)
A  LVX6048/2026-05-01.md                      (this file)

How to verify

sudo systemctl restart powermon.service powermon2.service

# Watch one PIRI cycle (≤5 min) — apparent power should NOT publish a 6000:
mosquitto_sub -h 10.0.0.41 -u mqtt -P <pass> \
    -t 'homeassistant/sensor/lvx6048_+_ac_output_apparent_power/state' -W 360

# Or query Influx after one full cycle:
influx -host 10.0.0.41 -username homeassistant -password <pass> \
    -database homeassistant -execute "
SELECT count(\"value\") FROM \"VA\"
WHERE (\"entity_id\" = 'lvx6048_lvx6048_1_ac_output_apparent_power'
    OR \"entity_id\" = 'lvx6048_lvx6048_2_ac_output_apparent_power')
  AND \"value\" = 6000
  AND time > now() - 30m"
# Expect: count → 0 once the next two PIRI cycles have passed without spikes.

Rollback

git -C ~/solar checkout HEAD~1 -- LVX6048/config/powermon/
cp ~/solar/LVX6048/config/powermon/powermon{,2}.yaml ~/.config/powermon/
# (re-edit ~/.config/powermon/*.yaml to restore real MQTT_PASSWORD)
sudo systemctl restart powermon.service powermon2.service

Upstream-fix candidate

Cleaner (but invasive) alternative would patch outputformats/hass.py to namespace entity_ids by command (e.g., _settings_ infix for PIRI). Not worth the patch maintenance — the excl_filter is one line per command and survives powermon upgrades.