# LVX6048 settings profile. Edit freely; all keys are optional. # `flash.py diff` previews changes; `flash.py apply --confirm` writes. # enum: AGM | FLOODED | USER battery_type: AGM # V 40.0..48.0 — hard shutdown; must be < stop_discharge_voltage. Only honored when battery_type=USER. cutoff_voltage: 40.8 # V 44.0..51.0 — switch battery→grid below this (pair: stop_charge_voltage). Only honored when battery_type=USER. stop_discharge_voltage: 46.0 # V 48.0..58.4 — CC→CV transition (pair: float_voltage; must be >= float_voltage). Only honored when battery_type=USER. bulk_voltage: 56.4 # A 2,10,20,30,40,50,60,70,80 — grid-side cap only max_utility_charging_current: 30 # A 10,20,30,40,50,60,70,80 — combined solar+AC cap max_charging_current: 60 # enum: solar_utility_battery | solar_battery_utility output_source_priority: solar_battery_utility # enum: solar_first | solar_and_utility | solar_only charger_priority: solar_first # enum: battery_load_utility_ac | load_battery_utility solar_power_priority: battery_load_utility_ac # enum: enabled | disabled (PEI/PDI) grid_tie: disabled # V 0 (=Full) or 48.0..58.0 — switch grid→battery above this (pair: stop_discharge_voltage). Only honored when battery_type=USER. stop_charge_voltage: 54.0 # V 48.0..58.4 — held while on grid (pair: bulk_voltage; must be <= bulk_voltage). Only honored when battery_type=USER. float_voltage: 54.0