4bfa021719 Fix POP01 encoding bug + harden grid-cal revert verification
Root cause of the grid-calibration auto-revert silently failing: lvx-control
and flash.py encode output_priority solar_battery_utility as "POP01", but PI18
POP is single-digit — the inverter silently rejects "POP01" (raw "POP1" works,
matches the POP_PIRI decoder). Compounded by powermon's adhoc queue wedging,
which dropped commands entirely until a restart. So the monitor logged "revert
done" while the cluster sat in SUB/grid mode for ~1.5h (no harm: battery full,
just running loads on grid).

- lvx-control + flash.py: POP_MAP "01" -> "1" (also patched the live
  /usr/local/bin/lvx-control + restarted; verified it now emits POP1).
- grid-cal-monitor: revert now VERIFIES via behavior (line_power_direction
  leaves 'input'), and on failure restarts powermon and re-sends raw POP1/PCP0,0,
  with a loud manual-fallback message. No more trust-the-publish.

Recovery for the live run: restarted powermon (unstuck adhoc) + raw POP1 + PCP0,0;
confirmed POP=Solar-Battery-Utility, PCP=Solar First, mode=Battery, line_dir=donothing.

Co-Authored-By: Claude Opus 4.8 (1M context) <noreply@anthropic.com>