Grid calibration: correct lever is output-priority SUB, add grid-cal-monitor
Discovered live 2026-06-25 driving an actual grid calibration: forcing a full grid charge is done via OUTPUT PRIORITY, not voltage thresholds. - SBU (everyday) won't grid-charge unless the bank is critically low; setting charger_priority=solar_and_utility alone does nothing at 52V. - SUB (output_priority=solar_utility_battery) runs loads on grid AND charges the battery to full. Combined with charger_priority=solar_and_utility, grid charging engages (device_mode->Hybrid/Line, line_dir->input, pack current jumps to ~120A). - Both POP/PCP set via lvx-control (all-mode-safe, atomic, no flash/USB). Revert POP->solar_battery_utility, PCP->solar_first when done. The re_discharge/flash.py approach is dead (firmware NAKs stop_charge>float); profile eg4-lp4-v2-calibration.yaml marked DEPRECATED. - grid-cal-monitor: supervises a SUB grid charge, safety aborts (cell>3.60V/ temp>45C), detects re-anchor (all 6 packs ->100%), auto-reverts POP+PCP (trap). - calibration-charge skill §3 rewritten to the POP lever. Co-Authored-By: Claude Opus 4.8 (1M context) <noreply@anthropic.com>
This commit is contained in:
@@ -7,6 +7,12 @@
|
||||
# / high-load stretches the bank may go weeks without a full charge and the coulomb
|
||||
# counters drift (e.g. pack 6 read 76% while physically at ~53% on 2026-06-24).
|
||||
#
|
||||
# !!! DEPRECATED 2026-06-25 — DO NOT USE. The re_discharge lever does not work for
|
||||
# grid calibration: firmware NAKs stop_charge_voltage above float (56 > 54), and it's
|
||||
# the wrong mechanism anyway. The CORRECT grid-charge lever is output priority -> SUB
|
||||
# (solar_utility_battery) via lvx-control — see the calibration-charge skill §3 and
|
||||
# memory project_lvx6048_grid_charge_lever. Kept only as a record of the dead end.
|
||||
#
|
||||
# !!! 2026-06-24 FINDING — grid-assist lever corrected, still UNVALIDATED !!!
|
||||
# The original idea (stop_charge_voltage: 0 = "Full") was REJECTED by the firmware:
|
||||
# `flash.py apply` got an inverter NAK on `BUCD480,000` on BOTH units (no change made).
|
||||
|
||||