# LVX6048 settings profile — EG4 LifePower4 v2 LiFePO4 bank, open-loop.
|
|
|
|
|
|
#
|
2026-06-24 12:25:48 -04:00
|
|
|
|
# Designed for: 6× EG4 LP4 v2 100 Ah in parallel (600 Ah, ~30.7 kWh).
|
|
|
|
|
|
# (Was 3 packs originally; 3 more added — commit 38ac9ca. Values below are
|
|
|
|
|
|
# unchanged and remain correct for 6 packs — they're only MORE conservative now.)
|
2026-04-26 19:26:44 -04:00
|
|
|
|
# Apply identically to both inverters in a parallel pair:
|
|
|
|
|
|
# sudo systemctl stop powermon.service powermon2.service
|
|
|
|
|
|
# ./flash.py apply --device /dev/lvx6048-1 --profile profiles/eg4-lp4-v2.yaml --confirm
|
|
|
|
|
|
# ./flash.py apply --device /dev/lvx6048-2 --profile profiles/eg4-lp4-v2.yaml --confirm
|
|
|
|
|
|
# sudo systemctl start powermon.service powermon2.service
|
|
|
|
|
|
# ./flash.py compare --device-a /dev/lvx6048-1 --device-b /dev/lvx6048-2
|
|
|
|
|
|
# ./flash.py sync-check --device-a /dev/lvx6048-1 --device-b /dev/lvx6048-2
|
|
|
|
|
|
#
|
|
|
|
|
|
# Voltage rationale (16S LFP, 3.2 V/cell nominal = 51.2 V pack):
|
|
|
|
|
|
# bulk 56.4 V = 3.525 V/cell — long-life sweet spot for LFP
|
|
|
|
|
|
# float 54.0 V = 3.375 V/cell — rest near mid-knee, avoid sitting on the top
|
|
|
|
|
|
# stop_charge 54.0 V — grid charges only to ~mid-knee; solar handles the bulk top-off
|
|
|
|
|
|
# stop_dis 48.0 V = 3.000 V/cell — soft "switch to grid" point
|
|
|
|
|
|
# cutoff 48.0 V = 3.000 V/cell — inverter hard shutdown floor (BMS still protects below)
|
2026-06-24 12:28:44 -04:00
|
|
|
|
# (Floor reviewed 2026-06-24: deliberately kept at 48.0/3.00 V for cycle-life margin.
|
|
|
|
|
|
# Lowering to 46-47 V would unlock only a few % of usable LFP capacity and isn't
|
|
|
|
|
|
# worth the deeper cycling on this large, non-capacity-constrained bank.)
|
2026-04-26 19:26:44 -04:00
|
|
|
|
# Conservative off-grid policy: keep grid as a soft top-up, let solar do the bulk work.
|
|
|
|
|
|
#
|
2026-06-24 12:25:48 -04:00
|
|
|
|
# Current rationale (600 Ah bank):
|
|
|
|
|
|
# 60 A/unit × 2 units = 120 A combined ≈ 0.2 C — very gentle on a 600 Ah bank.
|
|
|
|
|
|
# 30 A/unit MUCHGC keeps grid-charging conservative (60 A combined).
|
2026-06-24 14:41:32 -04:00
|
|
|
|
# Charge-current headroom — REVISIT (corrected 2026-06-24): an off-peak sample
|
|
|
|
|
|
# (71 A of 120 A) first suggested no clipping, but at the actual solar PEAK (13:44,
|
|
|
|
|
|
# ~9.5 kW PV) the bank was pinned AT the 120 A cap (121 A) with SoC only 65% and
|
|
|
|
|
|
# load just 3.3 kW. So at noon the charge cap likely IS throttling harvest. Before
|
|
|
|
|
|
# raising to 80 A/unit, run the throttle test: on a clear noon, lift the cap (or add
|
|
|
|
|
|
# load) and see if combined PV climbs above ~9.5 kW (MPPT voltage staying at Vmp). If
|
|
|
|
|
|
# it does, raise max_charging_current; if PV stays flat, the array is tilt/heat/shade
|
|
|
|
|
|
# limited (45 deg tilt + trees), not cap limited. See memory project_solar_array_config.
|
2026-04-26 19:26:44 -04:00
|
|
|
|
|
|
|
|
|
|
# enum: AGM | FLOODED | USER
|
|
|
|
|
|
# USER required to enable the per-cell custom voltages below.
|
|
|
|
|
|
battery_type: USER
|
|
|
|
|
|
|
|
|
|
|
|
# V 40.0..48.0 — hard shutdown; must be < stop_discharge_voltage.
|
|
|
|
|
|
cutoff_voltage: 48.0
|
|
|
|
|
|
|
|
|
|
|
|
# V 44.0..51.0 — switch battery→grid below this (pair: stop_charge_voltage).
|
|
|
|
|
|
stop_discharge_voltage: 48.0
|
|
|
|
|
|
|
|
|
|
|
|
# V 0 (=Full) or 48.0..58.0 — switch grid→battery above this. 0 = let bulk define.
|
|
|
|
|
|
stop_charge_voltage: 54.0
|
|
|
|
|
|
|
|
|
|
|
|
# V 48.0..58.4 — CC→CV transition (pair: float_voltage; must be >= float_voltage).
|
|
|
|
|
|
bulk_voltage: 56.4
|
|
|
|
|
|
|
|
|
|
|
|
# V 48.0..58.4 — held while on grid (pair: bulk_voltage; must be <= bulk_voltage).
|
|
|
|
|
|
float_voltage: 54.0
|
|
|
|
|
|
|
|
|
|
|
|
# A 10,20,30,40,50,60,70,80 — combined solar+AC cap, per unit.
|
|
|
|
|
|
max_charging_current: 60
|
|
|
|
|
|
|
|
|
|
|
|
# A 2,10,20,30,40,50,60,70,80 — grid-side cap, per unit.
|
|
|
|
|
|
max_utility_charging_current: 30
|
|
|
|
|
|
|
|
|
|
|
|
# enum: solar_utility_battery | solar_battery_utility
|
|
|
|
|
|
output_source_priority: solar_battery_utility
|
|
|
|
|
|
|
|
|
|
|
|
# enum: solar_first | solar_and_utility | solar_only
|
|
|
|
|
|
charger_priority: solar_first
|
|
|
|
|
|
|
|
|
|
|
|
# enum: battery_load_utility_ac | load_battery_utility
|
|
|
|
|
|
solar_power_priority: battery_load_utility_ac
|
|
|
|
|
|
|
|
|
|
|
|
# enum: enabled | disabled (PEI/PDI)
|
|
|
|
|
|
grid_tie: disabled
|