# lvx-control
Tiny daemon that bridges Home-Assistant-friendly MQTT topics to powermon's
adhoc-command queue, so HA buttons / selects / numbers can drive the LVX6048
pair without anyone touching the LCD or the shell.
## What it does
```
HA dashboard (mqtt button)
│ payload "solar_battery_utility"
solar/control/lvx6048/output_priority (subscribed by lvx-control)
│ validates against the allow-list, encodes to PI18
│ e.g. "POP01" (output source = solar -> battery -> utility)
powermon/lvx6048_1/addcommand ┐ mirrored to BOTH inverters in
powermon/lvx6048_2/addcommand ┘ the same publish so the parallel
cluster never desyncs (fault 86)
powermon services execute the command on each unit; result lands in
powermon/lvx6048_{1,2}/result for HA to confirm
```
## Supported actions
Friendly topic suffix → PI18 setter:
| Topic suffix | Payload values | PI18 |
|-------------------------------------|------------------------------------------------------------------------------------------------------|------|
| `output_priority` | `solar_utility_battery` \| `solar_battery_utility` | POP |
| `charger_priority` | `solar_first` \| `solar_and_utility` \| `solar_only` | PCP |
| `solar_power_priority` | `battery_load_utility_ac` \| `load_battery_utility` | PSP |
| `max_charging_current` | `10`,`20`,`30`,`40`,`50`,`60`,`70`,`80` (combined solar+AC, A) | MCHGC |
| `max_utility_charging_current` | `2`,`10`,`20`,`30`,`40`,`50`,`60`,`70`,`80` (grid-side, A) | MUCHGC |
Risky setters (battery thresholds, type, output mode, factory reset) are
intentionally **not** exposed here — those should go through
`lvx-flash/flash.py apply` with an explicit profile and confirmation.
### Known limitation
`max_charging_current` (MCHGC) and `max_utility_charging_current` (MUCHGC)
return `Failed` via PI18 when the inverter is actively charging (mode 06)
— the firmware appears to lock these setters during charge cycles. Other
setters (POP / PCP / PSP / PEI / PDI) work in all observed modes. If you
need to reliably change the charge-current caps, either:
- wait for the inverter to settle into Standby (mode 01) and retry, or
- change via the LCD (Programs 02 / 11), or
- use `lvx-flash/flash.py apply` (it stops the powermon services first,
giving exclusive USB access).
Track the `result` topic to see the actual outcome of each command.
## Quick test
```bash
# subscribe to results in another terminal
mosquitto_sub -h <broker> -u mqtt -P <pass> -v \
-t 'powermon/lvx6048_1/result' \
-t 'powermon/lvx6048_2/result'
# fire a control command
mosquitto_pub -h <broker> -u mqtt -P <pass> \
-t 'solar/control/lvx6048/charger_priority' \
-m 'solar_first'
```
You should see the encoded `PCP0,0` show up at the inverters' result topics
within ~1 second, and the existing PIRI sensor in HA will reflect the new
state on the next 5-minute cycle.
## Files
```
lvx-control/lvx-control <-- single-file Python (PEP-723 deps)
lvx-control/README.md <-- this file
etc/systemd/system/lvx-control.service
```
`install.sh` copies the script to `/usr/local/bin/lvx-control` and enables
the systemd unit. Broker credentials are read from
`~/.config/powermon/powermon.yaml` (no separate secret file).